MQTT Signal Reference

Complete reference of the 88 signals exposed by vito2mqtt over MQTT. These exposed signals are organized into 7 domain groups, each published as a JSON object to its own MQTT topic. An additional internal command (system_time) exists in the registry but is not exposed via these topics.


Topic Layout

Topics follow the domain-grouped layout defined in ADR-002:

vito2mqtt/{device_id}/{group}/state    # Telemetry (read-only, JSON)
vito2mqtt/{device_id}/{group}/set      # Commands (writable, JSON)

With the default device_id of vitodens200w, example topics:

vito2mqtt/vitodens200w/outdoor/state
vito2mqtt/vitodens200w/hot_water/state
vito2mqtt/vitodens200w/hot_water/set
vito2mqtt/vitodens200w/burner/state
vito2mqtt/vitodens200w/heating_radiator/state
vito2mqtt/vitodens200w/heating_radiator/set
vito2mqtt/vitodens200w/heating_floor/state
vito2mqtt/vitodens200w/heating_floor/set
vito2mqtt/vitodens200w/system/state
vito2mqtt/vitodens200w/system/set
vito2mqtt/vitodens200w/diagnosis/state

Signal Groups

Outdoor (3 telemetry signals)

Topic: vito2mqtt/{device_id}/outdoor/state

Signal Name Address Type Access Description
outdoor_temperature 0x0800 IS10 READ Current outdoor temperature (°C, ÷10)
outdoor_temperature_lowpass 0x5525 IS10 READ Low-pass filtered outdoor temperature (°C)
outdoor_temperature_damped 0x5527 IS10 READ Damped outdoor temperature (°C)

Hot Water (2 telemetry + 9 command signals)

Telemetry topic: vito2mqtt/{device_id}/hot_water/state

Signal Name Address Type Access Description
hot_water_temperature 0x0804 IS10 READ Current hot water temperature (°C)
hot_water_outlet_temperature 0x0814 IS10 READ Hot water outlet temperature (°C)

Command topic: vito2mqtt/{device_id}/hot_water/set

Signal Name Address Type Access Description
hot_water_setpoint 0x6300 IUNON READ_WRITE Target hot water temperature (°C)
hot_water_pump_overrun 0x6762 IUNON READ_WRITE Pump overrun time (seconds)
timer_hw_monday 0x2100 CT READ_WRITE Monday hot water schedule
timer_hw_tuesday 0x2108 CT READ_WRITE Tuesday hot water schedule
timer_hw_wednesday 0x2110 CT READ_WRITE Wednesday hot water schedule
timer_hw_thursday 0x2118 CT READ_WRITE Thursday hot water schedule
timer_hw_friday 0x2120 CT READ_WRITE Friday hot water schedule
timer_hw_saturday 0x2128 CT READ_WRITE Saturday hot water schedule
timer_hw_sunday 0x2130 CT READ_WRITE Sunday hot water schedule

Burner (8 telemetry signals)

Topic: vito2mqtt/{device_id}/burner/state

Signal Name Address Type Access Description
boiler_temperature 0x0802 IS10 READ Current boiler water temperature (°C)
boiler_temperature_lowpass 0x0810 IS10 READ Low-pass filtered boiler temperature (°C)
boiler_temperature_setpoint 0x555A IS10 READ Target boiler temperature (°C)
exhaust_temperature 0x0808 IS10 READ Exhaust gas temperature (°C)
burner_modulation 0x55D3 IUNON READ Current burner modulation (%)
burner_starts 0x088A IUNON READ Total burner start count
burner_hours_stage1 0x08A7 IU3600 READ Stage 1 operating hours
plant_power_output 0xA38F PR3 READ Current power output (%)

Heating Radiator / M1 (7 telemetry + 13 command signals)

The M1 heating circuit controls traditional radiators.

Telemetry topic: vito2mqtt/{device_id}/heating_radiator/state

Signal Name Address Type Access Description
flow_temperature_m1 0x2900 IS10 READ Flow temperature, radiator circuit (°C)
flow_temperature_setpoint_m1 0x2544 IS10 READ Flow temperature setpoint, radiator circuit (°C)
pump_status_m1 0x7663 IUNON READ Radiator circuit pump status
frost_warning_m1 0x2500 IUNON READ Frost warning flag, radiator circuit
frost_limit_m1 0x27A3 IUNON READ Frost limit temperature, radiator circuit (°C)
operating_mode_m1 0x2301 BA READ Operating mode, radiator circuit
operating_mode_economy_m1 0x2302 BA READ Economy mode, radiator circuit

Command topic: vito2mqtt/{device_id}/heating_radiator/set

Signal Name Address Type Access Description
heating_curve_gradient_m1 0x27D3 IS10 READ_WRITE Heating curve gradient, radiator circuit
heating_curve_level_m1 0x27D4 IUNON READ_WRITE Heating curve level, radiator circuit
room_temperature_setpoint_m1 0x2306 IUNON READ_WRITE Room temperature setpoint, radiator circuit (°C)
room_temperature_setpoint_economy_m1 0x2307 IUNON READ_WRITE Economy room temperature setpoint, radiator circuit (°C)
room_temperature_setpoint_party_m1 0x2308 IUNON READ_WRITE Party mode room temperature setpoint, radiator circuit (°C)
operating_mode_party_m1 0x2303 BA READ_WRITE Party mode toggle, radiator circuit
timer_m1_monday 0x2000 CT READ_WRITE Monday heating schedule, radiator circuit
timer_m1_tuesday 0x2008 CT READ_WRITE Tuesday heating schedule, radiator circuit
timer_m1_wednesday 0x2010 CT READ_WRITE Wednesday heating schedule, radiator circuit
timer_m1_thursday 0x2018 CT READ_WRITE Thursday heating schedule, radiator circuit
timer_m1_friday 0x2020 CT READ_WRITE Friday heating schedule, radiator circuit
timer_m1_saturday 0x2028 CT READ_WRITE Saturday heating schedule, radiator circuit
timer_m1_sunday 0x2030 CT READ_WRITE Sunday heating schedule, radiator circuit

Heating Floor / M2 (8 telemetry + 13 command signals)

The M2 heating circuit controls underfloor heating.

Telemetry topic: vito2mqtt/{device_id}/heating_floor/state

Signal Name Address Type Access Description
flow_temperature_m2 0x3900 IS10 READ Flow temperature, floor heating circuit (°C)
flow_temperature_setpoint_m2 0x3544 IS10 READ Flow temperature setpoint, floor heating circuit (°C)
pump_status_m2 0x7665 RT READ Floor heating circuit pump status
pump_speed_m2 0x7665 PR2 READ Floor heating circuit pump speed (%)
frost_warning_m2 0x3500 IUNON READ Frost warning flag, floor heating circuit
frost_limit_m2 0x37A3 IUNON READ Frost limit temperature, floor heating circuit (°C)
operating_mode_m2 0x3301 BA READ Operating mode, floor heating circuit
operating_mode_economy_m2 0x3302 BA READ Economy mode, floor heating circuit

Command topic: vito2mqtt/{device_id}/heating_floor/set

Signal Name Address Type Access Description
heating_curve_gradient_m2 0x37D3 IS10 READ_WRITE Heating curve gradient, floor heating circuit
heating_curve_level_m2 0x37D4 IUNON READ_WRITE Heating curve level, floor heating circuit
room_temperature_setpoint_m2 0x3306 IUNON READ_WRITE Room temperature setpoint, floor heating circuit (°C)
room_temperature_setpoint_economy_m2 0x3307 IUNON READ_WRITE Economy room temperature setpoint, floor heating circuit (°C)
room_temperature_setpoint_party_m2 0x3308 IUNON READ_WRITE Party mode room temperature setpoint, floor heating circuit (°C)
operating_mode_party_m2 0x3303 BA READ_WRITE Party mode toggle, floor heating circuit
timer_m2_monday 0x3000 CT READ_WRITE Monday heating schedule, floor heating circuit
timer_m2_tuesday 0x3008 CT READ_WRITE Tuesday heating schedule, floor heating circuit
timer_m2_wednesday 0x3010 CT READ_WRITE Wednesday heating schedule, floor heating circuit
timer_m2_thursday 0x3018 CT READ_WRITE Thursday heating schedule, floor heating circuit
timer_m2_friday 0x3020 CT READ_WRITE Friday heating schedule, floor heating circuit
timer_m2_saturday 0x3028 CT READ_WRITE Saturday heating schedule, floor heating circuit
timer_m2_sunday 0x3030 CT READ_WRITE Sunday heating schedule, floor heating circuit

System (7 telemetry + 7 command signals)

Telemetry topic: vito2mqtt/{device_id}/system/state

Signal Name Address Type Access Description
storage_temperature_lowpass 0x0812 IS10 READ Low-pass filtered storage temperature (°C)
internal_pump_status 0x7660 RT READ Internal pump on/off status
internal_pump_speed 0x7660 PR2 READ Internal pump speed (%)
storage_charge_pump_status 0x6513 RT READ Storage charge pump on/off status
circulation_pump_status 0x6515 RT READ Circulation pump on/off status
switch_valve_status 0x0A10 USV READ Switch valve position
flow_temperature_setpoint_m3 0x4544 IS10 READ Flow temperature setpoint, M3 circuit (°C)

Command topic: vito2mqtt/{device_id}/system/set

Signal Name Address Type Access Description
timer_cp_monday 0x2200 CT READ_WRITE Monday circulation pump schedule
timer_cp_tuesday 0x2208 CT READ_WRITE Tuesday circulation pump schedule
timer_cp_wednesday 0x2210 CT READ_WRITE Wednesday circulation pump schedule
timer_cp_thursday 0x2218 CT READ_WRITE Thursday circulation pump schedule
timer_cp_friday 0x2220 CT READ_WRITE Friday circulation pump schedule
timer_cp_saturday 0x2228 CT READ_WRITE Saturday circulation pump schedule
timer_cp_sunday 0x2230 CT READ_WRITE Sunday circulation pump schedule

Diagnosis (11 telemetry signals)

Topic: vito2mqtt/{device_id}/diagnosis/state

Signal Name Address Type Access Description
error_status 0x0A82 RT READ Current error status (0 = OK)
error_history_1 0x7507 ES READ Most recent error entry
error_history_2 0x7510 ES READ 2nd error history entry
error_history_3 0x7519 ES READ 3rd error history entry
error_history_4 0x7522 ES READ 4th error history entry
error_history_5 0x752B ES READ 5th error history entry
error_history_6 0x7534 ES READ 6th error history entry
error_history_7 0x753D ES READ 7th error history entry
error_history_8 0x7546 ES READ 8th error history entry
error_history_9 0x754F ES READ 9th error history entry
error_history_10 0x7558 ES READ 10th (oldest) error history entry

Signal Totals Summary

Group Telemetry Commands Total
Outdoor 3 3
Hot Water 2 9 11
Burner 8 8
Heating Radiator (M1) 7 13 20
Heating Floor (M2) 8 13 21
System 7 7 14
Diagnosis 11 11
Total 46 42 88

89 vs 88

The command registry contains 89 entries total. The system_time command (0x088E, type TI, WRITE-only) is used internally and not exposed through telemetry or command groups.


Type Code Reference

Code Name Description Unit
IS10 Signed fixed-point ÷10 Signed 16-bit integer divided by 10. Used for temperature values. °C
IUNON Unsigned integer Unsigned integer with no scaling. Used for counts, setpoints, status flags. varies
IU3600 Unsigned ÷3600 Unsigned integer divided by 3600. Converts seconds to hours. hours
PR2 Second byte unsigned Extracts the second byte as an unsigned percentage. Used for pump/fan speed. %
PR3 First byte ÷2 Extracts the first byte and divides by 2. Used for power output percentage. %
BA Betriebsart Operating mode enum. Labels are language-configurable (DE/EN) per ADR-006. enum
USV Umschaltventil Switch valve state enum. Labels are language-configurable (DE/EN). enum
ES Fehlerspeicher Error history entry: error code + BCD-packed timestamp. [label, datetime]
RT ReturnStatus Boolean/status flag as IntEnum: 0=OFF, 1=ON, 3=UNKNOWN, 0xAA=ERROR. 0/1
CT CycleTime Weekly timer schedule with 4 on/off time slot pairs per day. schedule
TI SystemTime BCD-packed date/time (8 bytes). Used for system clock sync. datetime

Command Payloads

Writing values

To write values, publish a JSON object to the group's /set topic:

# Set hot water target temperature to 55°C
mosquitto_pub -h localhost \
  -t 'vito2mqtt/vitodens200w/hot_water/set' \
  -m '{"hot_water_setpoint": 55}'

Multiple signals can be set in a single message:

# Set both room setpoint and economy setpoint for the radiator circuit
mosquitto_pub -h localhost \
  -t 'vito2mqtt/vitodens200w/heating_radiator/set' \
  -m '{"room_temperature_setpoint_m1": 21, "room_temperature_setpoint_economy_m1": 18}'

Read-before-write optimization

For READ_WRITE signals, vito2mqtt reads the current value from the boiler before writing. If the desired value matches the current value, the write is skipped. This reduces serial bus traffic and avoids unnecessary EEPROM wear on the boiler controller.

The __force meta-key

To bypass the read-before-write comparison and write unconditionally, include the __force key set to true:

{
  "hot_water_setpoint": 55,
  "__force": true
}

Use __force sparingly

Forcing writes bypasses the EEPROM wear protection. Only use this when you need to guarantee a write regardless of current state — e.g., after a boiler reset or when debugging.

Timer schedule format (CT type)

Timer schedules use the CycleTime format with 4 on/off slot pairs per day:

{
  "timer_hw_monday": [
    ["06:00", "08:00"],
    ["17:00", "22:00"],
    ["00:00", "00:00"],
    ["00:00", "00:00"]
  ]
}

Each slot is a [start, end] pair in "HH:MM" format. Unused slots should be set to ["00:00", "00:00"].